Download | - View final version: Équilibrage des pressions dans les murs à écran pare-pluie (PDF, 456 KiB)
|
---|
DOI | Resolve DOI: https://doi.org/10.4224/40002925 |
---|
Author | Search for: Rousseau, M. Z.1; Search for: Poirier, G. F.1; Search for: Brown, W. C.1 |
---|
Affiliation | - National Research Council of Canada. NRC Institute for Research in Construction
|
---|
Format | Text, Issue |
---|
Physical description | 6 p. |
---|
Subject | Rainscreen walls |
---|
Abstract | If the pressure in the air chamber behind the rainscreen is less than the pressure in front of it, rain is actually driven into the air chamber, which is, of course, undesirable. Through pressure equalization, this pressure difference is eliminated. A rainscreen wall has vent holes through which air can flow quickly to achieve pressure equalization. Two types of pressures -- static and dynamic -- have to be considered when calculating the size of the vent holes. Also, the pressure in an air chamber is not constant across the facade of a wall. That needs to be considered in their placement. |
---|
Publication date | 1998-07-01 |
---|
Publisher | Conseil national de recherches du Canada. Institut de recherche en construction |
---|
Series | |
---|
Translation of | |
---|
Language | French |
---|
Peer reviewed | No |
---|
NPARC number | 21274888 |
---|