Download | - View accepted manuscript: Oxidation and thermal resistance of HMW-PE and XLPE HV (PDF, 512 KiB)
|
---|
DOI | Resolve DOI: https://doi.org/10.1109/ELINSL.1988.13909 |
---|
Author | Search for: Crine, J. P.; Search for: Haridoss, S.; Search for: Cole, Kenneth1; Search for: Bulinski, A. T.; Search for: Densley, R. J.; Search for: Bamji, S. S. |
---|
Affiliation | - National Research Council of Canada. NRC Industrial Materials Institute
|
---|
Format | Text, Article |
---|
Conference | Conference record of the 1988 IEEE International Symposium on Electrical Insulation, June 5-8, 1988, Cambridge, Massachusetts, USA |
---|
Subject | thermal resistance; oxidation; electrical resistance measurement; aging; infrared spectra; spectroscopy; cable insulation; fourier transforms; conductors; time measurement |
---|
Abstract | The thermal oxidation of the insulation of several unaged and aged transmission and distribution cables has been measured by Fourier transform infrared (FTIR) spectroscopy. It is shown that all cables, even unaged ones, contain traces of oxidation which increases with aging, especially near the conductor shield. The antioxidant content has been investigated by FTIR and ultraviolet spectroscopy and sulfur content measurements. It is shown that the amount of residual antioxidant can be related to the oxidation induction time as measured by differential scanning calorimetry at 200 degrees C in oxygen. The influence of various parameters on cable thermal resistance is discussed. |
---|
Publication date | 1988-06-05 |
---|
Publisher | IEEE |
---|
In | |
---|
Language | English |
---|
Peer reviewed | Yes |
---|
NRC number | NRC-INMS-1744 |
---|
NPARC number | 8899270 |
---|
Export citation | Export as RIS |
---|
Report a correction | Report a correction (opens in a new tab) |
---|
Record identifier | 46d31cec-5527-4e14-8ff0-025e4aef08a5 |
---|
Record created | 2009-04-22 |
---|
Record modified | 2024-02-29 |
---|