| DOI | Resolve DOI: https://doi.org/10.1109/AMPS.2019.8897788 |
|---|
| Author | Search for: Rietveld, Gert; Search for: Fransen, Martin; Search for: Blanc, Nicolas V. F.; Search for: So, Eddy1 |
|---|
| Affiliation | - National Research Council Canada. Metrology Research Centre
|
|---|
| Format | Text, Article |
|---|
| Conference | 2019 IEEE 10th International Workshop on Applied Measurements for Power Systems (AMPS), September 25-27, 2019, Aachen, Germany |
|---|
| Subject | power; revenue metering; billing; substation; high voltage (HV); calibration; high current; current transformer; voltage transformer; power meter; precision measurements |
|---|
| Abstract | A three-phase reference system for in-situ calibration of High Voltage (HV) Revenue Metering Systems in substations has been established. It consists of a high-accuracy three-phase power meter, including corresponding current and voltage transformers (CTs and VTs). The reference system is capable of performing power measurements up to 150 kV system voltage and line currents up to 5000 A. The excellent results of the calibration and further testing of power meter, CTs, and VTs indicate that an overall system uncertainty of better than 100μW/VA can be achieved. |
|---|
| Publication date | 2019-11-14 |
|---|
| Publisher | IEEE |
|---|
| In | |
|---|
| Language | English |
|---|
| Peer reviewed | Yes |
|---|
| Export citation | Export as RIS |
|---|
| Report a correction | Report a correction (opens in a new tab) |
|---|
| Record identifier | ffb1ecc2-77ee-4076-bb33-1d3d2d85e06e |
|---|
| Record created | 2021-02-22 |
|---|
| Record modified | 2021-02-22 |
|---|