DOI | Trouver le DOI : https://doi.org/10.1016/j.firesaf.2012.08.006 |
---|
Auteur | Rechercher : Cree, D.; Rechercher : Chowdhury, E. U.; Rechercher : Green, M. F.; Rechercher : Bisby, L. A.; Rechercher : Bénichou, N.1 |
---|
Affiliation | - Conseil national de recherches du Canada. Construction
|
---|
Format | Texte, Article |
---|
Sujet | Fire test; FRP; Insulation; Reinforced concrete column; High temperature; Full-scale |
---|
Résumé | This research investigates the fire performance of one circular and one square reinforced concrete column strengthened with a fibre reinforced polymer (FRP) wrap and covered with a unique supplemental fire protection system. An experimental full-scale fire resistance test was conducted at the National Research Council of Canada. The insulated and strengthened FRP wrapped columns were exposed to the ULC-S101 standard fire and both columns obtained fire endurance ratings of over 4 h. Details of the fire endurance experiment on both columns are described in this paper. Additionally, numerical models developed specifically for circular and square columns are validated against the experimental results. |
---|
Date de publication | 2012-11 |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Identificateur | S0379711212001105 |
---|
Numéro NPARC | 21268758 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | 2548007c-9a57-4e43-9cf7-f5cb956bff0e |
---|
Enregistrement créé | 2013-11-12 |
---|
Enregistrement modifié | 2020-04-21 |
---|