DOI | Trouver le DOI : https://doi.org/10.1109/TIM.2019.2899184 |
---|
Auteur | Rechercher : So, E.1; Rechercher : Verhoeven, R.; Rechercher : Simons, B.; Rechercher : Parks, H. V.1; Rechercher : Angelo, D.1 |
---|
Affiliation | - Conseil national de recherches du Canada. Centre de recherche en métrologie
|
---|
Format | Texte, Article |
---|
Sujet | Current transformer (CT); extra high voltage (EHV); high current; loss measurements; multiratio; multistage; precision measurements; ratio errors; shunt reactor; three stage; uncertainty |
---|
Résumé | An overview of the development and performance of a special high precision multi-ratio three-stage CT and its application for loss measurements of EHV three-phase shunt reactors with test voltages up to a phase voltage of 1100 kV at Royal SMIT Transformers are presented and discussed. It features current ratios of 500 A/1 A, 400 A/1 A, 300 A/1 A, 200 A/1 A, and 100 A/1 A with ratio errors within 3 × 10⁻⁶ in both magnitude and phase with burdens up to 1.0 Ω and at power frequencies of 50-60 Hz. |
---|
Date de publication | 2019-03-18 |
---|
Maison d’édition | IEEE |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | 2cbd21fa-8221-4540-b7a7-f30a069a4f3c |
---|
Enregistrement créé | 2021-01-19 |
---|
Enregistrement modifié | 2021-09-17 |
---|