DOI | Trouver le DOI : https://doi.org/10.1260/2040-2317.5.4.353 |
---|
Auteur | Rechercher : Green, Mark; Rechercher : Hollingshead, Kevin; Rechercher : Bénichou, Noureddine1 |
---|
Affiliation | - Conseil national de recherches du Canada. Construction
|
---|
Format | Texte, Article |
---|
Sujet | Fire; Fibre Reinforced Polymers; Concrete; Strengthening; Repair; Rehabilitation |
---|
Résumé | This paper considers the fire performance of concrete beams and columns that have been strengthened with fibre reinforced polymers (FRPs). Results from four recent full-scale tests are presented. A newly developed type of insulation was employed and the thickness of the insulation (15 to 20 mm) was approximately half that provided in earlier tests. All of the members survived four hours of the fire exposure. A conceptual model for design to determine when insulation is required is also presented. Further research needed to fully develop the conceptual model to a more practical design tool is outlined. |
---|
Date de publication | 2014-11-18 |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro NPARC | 21276828 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | 6983ca1d-5607-4ea0-bda4-59397820c1c1 |
---|
Enregistrement créé | 2015-10-23 |
---|
Enregistrement modifié | 2020-04-22 |
---|