Téléchargement | - Voir le manuscrit accepté : A reference system for on-site calibration of high-voltage revenue metering systems (PDF, 682 Kio)
|
---|
DOI | Trouver le DOI : https://doi.org/10.1109/CPEM.2014.6898430 |
---|
Auteur | Rechercher : Rietveld, Gert; Rechercher : Fransen, Martin; Rechercher : Blanc, Nicolas; Rechercher : Houtzager, Ernest; Rechercher : So, Eddy1 |
---|
Affiliation | - Conseil national de recherches du Canada. Science des mesures et étalons
|
---|
Format | Texte, Article |
---|
Conférence | Precision Electromagnetic Measurements (CPEM 2014), 2014 Conference on, 24-29 August 2014, Rio de Janeiro |
---|
Sujet | power; revenue metering; billing; traceability; substation; high voltage (HV); high current; current transformer; voltage transformer; power meter; precision measurements |
---|
Résumé | A reference setup for on-site calibration and validation of revenue metering systems is realized. The system consists of a three-phase power meter and high-accuracy current and voltage transformers (CTs and VTs). Measurements can be made up to 150 kV (system voltage) and line currents up to 5000 A. The power meter, the CTs, and the VTs were all calibrated. Based on the excellent results of the calibration of these components it is possible to predict the full system performance with an accuracy of 35 J.lWNA. This estimation was verified with a full system validation, showing that the system is much more accurate than required and that detrimental effects to the accuracy are well understood. |
---|
Date de publication | 2014-08 |
---|
Maison d’édition | IEEE |
---|
Dans | |
---|
Série | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro NPARC | 21274914 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | c22963df-a587-4536-8eac-6511f8b59f0e |
---|
Enregistrement créé | 2015-04-28 |
---|
Enregistrement modifié | 2020-09-28 |
---|