DOI | Resolve DOI: https://doi.org/10.1109/61.193863 |
---|
Author | Search for: Arseneau, R.; Search for: Filipski, P. S. |
---|
Format | Text, Article |
---|
Abstract | The influence of harmonics on commonly used three-phase watthour and kVA demand meters was studied using a computer-controlled three-phase test system capable of generating nonsinusoidal voltages and currents. A description of the three-phase test system and results of preliminary tests of several revenue meters are presented. The performance of the tested meters is compared with the response of time-division and thermal reference meters for different harmonic conditions, primarily field-recorded data. Errors up to 2% were observed during the testing of energy meters and up to 35% for kVA demand meters. |
---|
Publication date | 1988-07 |
---|
Publisher | IEEE |
---|
In | |
---|
Language | English |
---|
Peer reviewed | Yes |
---|
NRC number | NRC-INMS-4339 |
---|
NPARC number | 5764594 |
---|
Export citation | Export as RIS |
---|
Report a correction | Report a correction (opens in a new tab) |
---|
Record identifier | dc9dacb0-d6e9-4db8-8303-69a96da92d08 |
---|
Record created | 2009-03-29 |
---|
Record modified | 2020-09-28 |
---|