DOI | Trouver le DOI : https://doi.org/10.1109/61.193863 |
---|
Auteur | Rechercher : Arseneau, R.; Rechercher : Filipski, P. S. |
---|
Format | Texte, Article |
---|
Résumé | The influence of harmonics on commonly used three-phase watthour and kVA demand meters was studied using a computer-controlled three-phase test system capable of generating nonsinusoidal voltages and currents. A description of the three-phase test system and results of preliminary tests of several revenue meters are presented. The performance of the tested meters is compared with the response of time-division and thermal reference meters for different harmonic conditions, primarily field-recorded data. Errors up to 2% were observed during the testing of energy meters and up to 35% for kVA demand meters. |
---|
Date de publication | 1988-07 |
---|
Maison d’édition | IEEE |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro du CNRC | NRC-INMS-4339 |
---|
Numéro NPARC | 5764594 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | dc9dacb0-d6e9-4db8-8303-69a96da92d08 |
---|
Enregistrement créé | 2009-03-29 |
---|
Enregistrement modifié | 2020-09-28 |
---|