Téléchargement | - Voir le manuscrit accepté : A computer-controlled system for calibrating high voltage revenue metering systems under actual operating conditions of high voltage and sinusoidal/non-sinusoidal voltage and current waveforms (PDF, 549 Kio)
|
---|
DOI | Trouver le DOI : https://doi.org/10.1109/CPEM.2010.5544827 |
---|
Auteur | Rechercher : So, E.1; Rechercher : Arseneau, R.1; Rechercher : Bennett, D.1; Rechercher : Frigault, M.1 |
---|
Affiliation | - Conseil national de recherches du Canada. Institut des étalons nationaux de mesure du CNRC
|
---|
Format | Texte, Article |
---|
Conférence | 2010 Conference on Precision Electromagnetic Measurements (CPEM 2010), June 13-18, 2010, Daejeon, South Korea |
---|
Résumé | The development of a computer-controlled system for the calibration of high voltage revenue metering systems under actual operating conditions of high voltage and sinusoidal/non-sinusoidal voltage and current waveforms will be described. Measurements can be made at any power factor from zero lag through unity, at voltages up to 100 kV line-to-ground voltage and currents up to 2000 A. The magnitude and phase uncertainties (k=2) are estimated to be not more than 50 μW/VA and 50 μrad, and 100 μW/VA and 100 μrad for sinusoidal and non-sinusoidal conditions, respectively. |
---|
Date de publication | 2010-06-01 |
---|
Dans | |
---|
Série | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro NPARC | 17131341 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | b80aaf68-26e3-453f-aec3-ceaeb695c79c |
---|
Enregistrement créé | 2011-03-11 |
---|
Enregistrement modifié | 2020-04-17 |
---|